Permit Number | FIR17-00293 |
Status | Finaled |
Name |
TRIBAL FIRE SYSTEMS
|
Site Address |
8000 S FEDERAL WAY
|
Project Name | Micron Bldg 51 |
Customer Number | |
ePlanReview | Yes |
Description |
[Micron Building #51 C24074 - System 20-7 Pyrophoric]
The fire sprinkler scope of work consists of protecting the pyrophoric room and the toxic gas monitoring room. In addition, and auxiliary dry system for 20-5 will be connected to the main. The room design is based on approved AMMR2.
[BLD16-03893]
** Foundation & shell only** **modification to complete mep portion of the work** For the construction of a 1,340 sq. ft. pyrophoric building with work to include the construction of the cold shell only per the approved plans and the attached alternate. This building is fully fire sprinklered and alarmed per H occupancy requirements. Alternate Means and Methods approval for this building attached to the plans. CDM
Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.
A.M.M.R. #2: Pyrophoric Bunker – Quantities exceed MAQs and are stored less than 50ft away. Proposed alternate is for a cut off room of 4hr rated cast in place concrete with no openings and that can withstand 100 psf load. All gas cylinders will be stored in fire sprinklered cabinets with UV/IR flame detection and gas monitoring. Proposed alternate to provide building at a minimum 5ft and zero inches from B51
|