Permit Information
Permit NumberFIR17-00318
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP B8 3rd Flr Remodel
Customer Number 
ePlanReviewYes
Description
HP B8 3rd Flr Remodel scope of work is to add notification devices due to the addition of new walls. We are relocating several wall horn strobes and adding new NAC panel with new NAC circuits. Associated with building permit BLD17-01371.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/17/201710/17/201710/17/2017PPASS
DetailsTroy Cobbley
Permit finaled

Colton Phone #: ###-####
INSP-Final Inspection9/26/20179/27/20179/27/2017APART
DetailsTroy Cobbley
Not ready for a final yet. I need as-builts showing the additional notification devices that have been added for walls that have not been installed yet. If the walls do not get installed then the as-builts need to reflect that. Also the security locks have not been installed on the south side doors for testing/release upon activation of fire alarm. I spoke to Colton with Simplex about this.
INSP-Alarm Testing7/27/20177/27/20177/27/2017PDONE
DetailsTroy Cobbley
Phase 1 (northwest quadrant) fire alarm complete.

Colton Phone #: ###-####
INSP-Alarm Testing7/25/20177/26/20177/26/2017AFAIL
DetailsTroy Cobbley
Todays inspection was for phase 1 (north west quadrant). Notification did function but the doors did not release upon activation of the fire alarm system. Building plans are going to be resubmitted to see if the door mags will be allowed.