Permit Information
Permit NumberFIR17-00352
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 7719 W PREECE DR
Project NameMarena Bldg 2 6plex
Customer Number 
ePlanReviewYes
Description
[Marena Building #2]
The fire sprinkler scope of work consists of two level six plex protected per NFPA 13R. The top level will have the piping tented. The sprinklers are residential type.
[BLD16-04308]
For the construction of an 8,555 sq. ft. six plex including the attached garages and the covered entries with 6, two story units and work to include general site work and construction of the new building per the approved plans. This building is fully fire sprinklered for R-2 occupancy. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/31/20182/1/20182/1/2018PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro1/25/20181/26/20181/26/2018PPASS
DetailsTroy Cobbley
Overhead hydro test passed
INSP-Supply line flush1/24/20181/25/20181/24/2018APASS
DetailsTroy Cobbley
Underground supply line flush passed
INSP-Sprinkler Rough-in11/16/201711/16/201711/16/2017PPASS
DetailsTroy Cobbley
Rough-in passed. Tenting passed. Piping is ok to cover
INSP-Sprinkler Rough-in11/14/201711/15/201711/15/2017AFAIL
DetailsTroy Cobbley
Resubmit plans showing all of the additional 90's on the first floor to verify that the hydraulic calculations still work. Also the plans need to be "mirrored" because piping and room layout is backwards. Also I'm requesting insulation to be installed below the piping in the garage and as per the general contractor he will do the installation. No piping can be covered.
INSP-Sprinkler Rough-in10/6/201710/9/201710/9/2017APASS
DetailsTroy Cobbley
Underground supply line inspection passed. Piping can be covered.