Permit Information
Permit NumberFIR17-00365
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 7997 W FRANKLIN RD
Project NameLonghorn Steak House
Customer NumberUDG ONLY
ePlanReviewYes
Description
[Longhorn Steakhouse - UDG Only] - Quick Permit
New 6" Fire Main point of connections to be after Tee and Valve for underground supply.

[BLD17-00729] - Permit to construct a new 5,593 sq., ft. assembly restaurant building and related site improvements. Scope of work includes: construction of footing foundation, slab on grade concrete floor, construction of wood stud framed exterior envelope walls, truss roof construction, construction of interior non-bearing walls to create lobby area, dining areas, bar area, commercial kitchen, walk-in cooler, office, mechanical room, storage closets and men’s and woman’s restrooms accessible to the disabled, new windows and accessible doors, new electrical, new mechanical, new plumbing, site work, and interior finishes to be in compliance with Ch. 8 of the 2012 IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. Note: Special Inspections Required see form 310. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/8/201712/8/201712/8/2017PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro10/19/201710/20/201710/20/2017APASS
DetailsJim Page
Hydrostatic test for underground supply complete.
INSP-Sprinkler Rough-in/Hydro10/16/201710/17/201710/17/2017ACANC
DetailsTroy Cobbley
Not ready for a hydro due to a leaking flange
INSP-Supply line flush10/12/201710/12/201710/12/2017PPASS
DetailsTroy Cobbley
Underground supply line flush passed
INSP-Sprinkler Rough-in10/11/201710/11/201710/11/2017PCANC
DetailsTroy Cobbley
Wrong permit called in for inspection.
INSP-Sprinkler Rough-in/Hydro8/31/20178/31/20178/31/2017PCANC
DetailsTroy Cobbley
Contact Brad Westbrook ###-#### 30 min prior to UG Hydro insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Sprinkler Rough-in8/10/20178/11/20178/11/2017APASS
DetailsTroy Cobbley
The piping for the remote FDC has the tape installed and can be covered.
INSP-Final Inspection8/10/20178/10/20178/10/2017PFAIL
DetailsTroy Cobbley
Project is not ready for a final yet. Will need hydro tests and flushing. Todays inspection was for the remaining remote FDC piping/vault. Piping can be covered up to the FDC. The FDC need the wrapping as per Chapter 10 of NFPA 13 prior to cover.
INSP-Sprinkler Rough-in8/8/20178/8/20178/8/2017PPASS
DetailsTroy Cobbley
Todays inspection was for a portion of the remote FDC. Piping is ok to cover up to the vault location. Vault was not installed yet.
INSP-Sprinkler Rough-in8/4/20178/4/20178/4/2017APART
DetailsTroy Cobbley
The underground supply piping is now installed deap enough and can be covered. The remote FDC piping has not been installed yet in the same trench. I will need another inspection scheduled prior to a complete cover inspection given.
INSP-Sprinkler Rough-in7/31/20178/1/20178/1/2017AFAIL
DetailsTroy Cobbley
The underground supply piping and the remote FDC piping do not meet the minimum 4'-6" bury depth as required per City Of Boise ordinance and Idaho State Fire Marshal requirements.
INSP-Final Inspection7/20/20177/20/20177/20/2017PCANC
DetailsTroy Cobbley
Contact will be Aaron Trimble please contact him 30 min. prior to Fire Final.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank