INSP-Final Inspection | 2/28/2018 | 3/1/2018 | 3/1/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Call prior to going Phone #: 2089853303 >> Inspection requested via mobile web by Mike Kroll
|
INSP-Final Inspection | 2/27/2018 | 2/27/2018 | 2/27/2018 | P | FAIL |
Troy Cobbley
|
|
|
Was unable to test the interconnection with the fire sprinkler system due to work being performed.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug
|
INSP-Final Inspection | 2/26/2018 | 2/26/2018 | 2/26/2018 | P | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa Inspection cancelled via mobile web on Monday, February 26, 2018.
|
INSP-Final Inspection | 2/22/2018 | 2/23/2018 | 2/23/2018 | A | PART |
Jim Page
|
|
|
Partial final inspection complete for fire alarms, checked interface between hood alarm activation and fire alarm panel, audio visual device inspection is complete, initiating devices have been inspected with exception to fire sprinkler components, tampers and flow switch will need to be tested after flush on underground has been completed, all in-duct detectors have been inspected, signals have been verified with monitoring service.
|