Permit Information
Permit NumberFIR17-00607
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 7655 N JENNIE LN
Project NameRIVER ACADEMY
Customer Number 
ePlanReviewYes
Description
[The River Academy]
The fire sprinkler scope of work consists of protecting a two-story building with a 3”
tree type system. The underground supply is 4”.

• The underground is under permit FIR16-00785

[BLD16-02979]
Permit for the construction of a new 10,030 sq. ft. 2 story building with 8,220 sq. ft. on the first story and 1,810 sq. ft. on the second story, work to include general sit and utility work and the construction of a two story wood framed structure per the approved plans and the attached engineering. This building is to be fully fire sprinklered. CDM

Alternative Materials and Methods:

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/27/20183/1/20183/1/2018APASS
DetailsTroy Cobbley
Permit finaled, Forward flush passed
INSP-Supply line flush2/27/20182/28/20182/27/2018PCANC
DetailsKatie Marron
Jeff from eagle water said he can be on site at 1:30 Phone #: ###-#### >> Inspection requested via web by Matthew Lewis Inspection cancelled from web by: Matthew Lewis
INSP-Final Inspection2/27/20182/27/20182/27/2018PFAIL
DetailsTroy Cobbley
Need the head guards installed and the coverage modified under the exterior canopy and the interconnection with the fire alarm panel tested..


Call prior to going Phone #: 20887175 >> Inspection requested via mobile web by Mike
INSP-Final Inspection2/27/20182/28/20182/27/2018PCANC
DetailsKatie Marron
Phone #: ###-#### >> Inspection requested via web by Matthew Lewis Inspection cancelled from web by: Matthew Lewis
INSP-Final Inspection2/22/20182/23/20182/23/2018AFAIL
DetailsJim Page
Upright heads in main level 1 hallway are to close to the deck, a minimum of 1 in is required. Provide fire sprinkler head on northside of commercial kitchen hood. Dry sidewalls on exterior canopy need to be relocated to provide proper coverage. Utility room next to kitchen has head to far off of wall, room is ordinary hazard and sprinkler head is to far off of wall. Provide heads gaurds on fire sprinkler heads located under stairs and stair landing on level 1.
INSP-Sprinkler Rough-in/Hydro2/22/20182/23/20182/23/2018ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge (Underground was not fushed by end of inspection, system was filled with hose from domestic water supply, overhead cannot be turned on until flush is complete, if overhead is turned on before flush then all sprinkler heads will be pulled and drained due to possible debris)
INSP-Sprinkler Rough-in12/27/201712/28/201712/28/2017APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
INSP-Sprinkler Rough-in12/26/201712/26/201712/26/2017PFAIL
DetailsJim Page
Provide fire sprinklers/piping for pendants in main lobby and area behind main lobby. Provide fire sprinkler next to commercial hood. Remove insulation that is caught on multiple heads in attic space.
INSP-Sprinkler Rough-in11/28/201711/29/201711/29/2017APART
DetailsJim Page
Partial rough to cover inspection complete for overhead fire sprinlkler piping, notated the city approved drawings areas approved for cover.
INSP-Sprinkler Rough-in/Hydro11/27/201711/28/201711/28/2017AFAIL
DetailsTroy Cobbley
No city approved plans or small documents on site. No inspection performed.

is only a partial inspection Phone #: ###-#### Inspection requested via web by Matthew Lewis