Permit Information
Permit NumberFIR17-00676
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 1424 N ORCHARD ST
Project NameMasonry Center
Customer Number 
ePlanReviewYes
Description
[Masonary Center] - Quick Permit
Add, plug and relocate sprinklers to accommodate new wall and ceiling configuration.
Change out sprinklers to new chrome pendent quick response type.

There does not seem to be an associated building permit at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/29/20201/31/20201/31/2020APASS
DetailsTroy Cobbley
Permit finaled

Contact is Chris, Please give thirty minutes heads up, will be coming from Nampa Phone #: ###-#### Inspection requested via web by Chris Green
INSP-Final Inspection12/14/201712/15/201712/15/2017AFAIL
DetailsTroy Cobbley
Project is not ready for a final at this time. It is however ready for a rough-to cover.. Too pendant heads in the office area are too close to a soffit and will need to be relocated. This work will be verified at final. The sprinkler piping in the Offices/under the Mezzanine can be covered. I noted that a large vertical chase has been constructed which is a large combustible concealed space and will need addressed prior to a cover.

Call Roy Fouts at ###-#### an hour before inspection. He will meet you there. Thanks! Phone #: ###-#### Inspection requested via web by Brett Lawatch