INSP-Final Inspection | 5/1/2018 | 5/1/2018 | 5/1/2018 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection complete.
|
INSP-Final Inspection | 2/9/2018 | 2/9/2018 | 2/9/2018 | P | PART |
Jim Page
|
|
|
Partial final fire sprinkler inspection complete, sprinkler heads need to be installed in verizon room located in the basement level, all other areas are complete for final fire sprinkler inspection.
|
INSP-Final Inspection | 1/11/2018 | 1/12/2018 | 1/12/2018 | A | PART |
Troy Cobbley
|
|
|
Only item tested was, per Brian, is the main flow switch. The flow switch I tested was located at the main riser in the basement. I noticed that all of the tamper switches on this riser in the basement had been lock/chained open. I can't final until all devices have been connected/tested.
Brian Phone #: ###-####
|
INSP-Final Inspection | 1/9/2018 | 1/10/2018 | 1/10/2018 | A | PART |
Jim Page
|
|
|
Partial final inspection for overhead fire sprinklers complete, fire alarms and fire sprinkler monitoring still needs to be installed, fire sprinkler permit cannot be finaled until associated fire alarm devices have been inspected and passed.
|
INSP-Sprinkler Rough-in/Hydro | 1/9/2018 | 1/9/2018 | 1/9/2018 | P | PASS |
Jim Page
|
|
|
Rough in inspection for overhead fire sprinkler piping on level 1 and basement level complete.
|
INSP-Sprinkler Rough-in/Hydro | 1/9/2018 | 1/9/2018 | 1/9/2018 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for basement overhead fire sprinkler piping witnessed, no observed pressure loss at riser gauge.
|
INSP-Sprinkler Rough-in/Hydro | 1/8/2018 | 1/8/2018 | 1/8/2018 | P | DONE |
Jim Page
|
|
|
Hydrostatic test witnessed for overhead fire sprinkler piping on levels 1 and 2, no loss of pressure observed at riser gauge.
|
INSP-Sprinkler Rough-in/Hydro | 1/8/2018 | 1/8/2018 | 1/8/2018 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for levels 2 and 3 for overhead fire sprinkler piping complete, approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 1/4/2018 | 1/5/2018 | 1/5/2018 | P | PART |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping on level 3 complete.
|