Permit Information
Permit NumberFIR18-00027
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2214 E GOODMAN ST
Project NameWARM SPRINGS APARTMENTS
Customer Number 
ePlanReviewYes
Description
[Warm Springs Apartments Building A & B]
The fire sprinkler scope of work consists of two three level building protected using a NFPA 13R systems with floor control valves. Piping is CPVC with residential sprinklers

• The underground piping is under permit FIR17-00579.
[BLD17-00954]
Building A - Permit for the construction of a 9 unit, 3 story wood framed apartment building with work to include general site work and construction of the new building per the approved plans. This building fire sprinklered with a NFPA-13R system. **JAR**

Building B - Permit for the construction of a 12 unit, 3 story wood framed apartment building with work to include general site work and construction of the new building per the approved plans. This building fire sprinklered with a NFPA-13R system. **JAR*

Alternative Materials and Methods:

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/23/20194/24/20194/24/2019APASS
DetailsJim Page
Final fire sprinkler inspection complete.

We would like to perform this in conjunction with fire alarm testing.
Please call Lonnie with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Sprinkler Rough-in7/24/20187/24/20187/24/2018APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete for buidling B levels 1, 2 and 3. General contractor needs to provide documentation for foam sheet insulation rating of installed an the deck, a minimum of R-38 is required for freeze protection on level 3, cover is approved at general contractors risk, if sheeting is not R-38 rated then any cover material over fire sprinkler piping will need to be removed and a R-38 or higher rating will need to be installed. Cover is approved for building A for overhead fire sprinkler piping.
INSP-Sprinkler Rough-in/Hydro7/23/20187/24/20187/24/2018ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauges.

RANDY IS OUR FOREMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt
INSP-Sprinkler Rough-in6/27/20186/27/20186/27/2018APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete for buidling A levels 1, 2 and 3. General contractor needs to provide documentation for foam sheet insulation rating of installed an the deck, a minimum of R-38 is required for freeze protection on level 3, cover is approved at general contractors risk, if sheeting is not R-38 rated then any cover material over fire sprinkler piping will need to be removed and a R-38 or higher rating will need to be installed. Cover is approved for building A for overhead fire sprinkler piping.
INSP-Sprinkler Rough-in/Hydro6/26/20186/27/20186/27/2018ADONE
DetailsJim Page
Hydrostatic test witnessed for overhhead fire sprinkler piping for levels 1, 2 and 3 Building A, no pressure loss observed at riser provided gauges.

RANDY CARTRIGHT IS OUR FOREMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt
INSP-Supply line flush6/22/20186/22/20186/22/2018PDONE
DetailsJim Page
Undergorund main line flush complete for both buildings.

Phone #: ###-#### Inspection requested via web by Christophe Wilson
INSP-Sprinkler Rough-in/Hydro6/22/20186/22/20186/22/2018ADONE
DetailsJim Page
Hydrostatic test witnessed for both underground main supplies, no pressure loss observed at conractor provided gauges.
INSP-Sprinkler Rough-in4/16/20184/17/20184/17/2018PCANC
DetailsJim Page
MIKE OSWALD IS OUR FOREMAN Phone #: ###-#### >> Inspection requested via web by Brad Bettencourt Inspection cancelled from web by: Brad Bettencourt