Permit Information
Permit NumberFIR18-00064
StatusIssued
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7500 W MOSSY CUP ST
Project NameNxEdge TI Phase 4
Customer Number 
ePlanReviewYes
Description
[NxEdge TI Phase 4]
Install 27 new pendent sprinklers on return bend in a common area due to new t-bar ceilings in this existing building on the existing fire sprinkler system.

There does not seem to be an associated building permit at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in5/29/20185/29/20185/29/2018PPASS
DetailsTroy Cobbley
Rough-in for the drops passed. Piping can be covered. Protection has been provided under overhead door.

Call Anthony to coordinate Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in5/23/20185/23/20185/23/2018PPASS
DetailsTroy Cobbley
Todays inspection was just for the drops from the existing branchlines. They all looked good. I noted that sprinkler coverage is missing under the overhead door and once the ceiling was installed under the door a combustible concealed space would be created that will require sprinkler protection.

Call Anthony to coordinate, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello