Permit NumberFIR18-00123
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 11880 W PRESIDENT DR Unit: A
Project NamePRESIDENT SUITE A
Customer Number 
ePlanReviewYes
Description
[President Suite A] - Quick Permit
RELOCATE 4 SPRINKLERS AND ADD 1 SPRINKLER, ADJUSTING TO NEW WALLS IN THE OFFICE AREA AND A NEW BATHROOM WALL.

[BLD17-04635]
To remodel an existing 3,750 sq ft office tenant space. Work to include demolition of various existing interior walls, construction of new interior walls to create office spaces, breakroom and shower room. Relocate front entrance and miscelaneous related finishes. This building is fully fire sprinklererd. Separate fire sprinkler and alarm permits will be required prior to any modifications; as regulated by the Fire Department. RmH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/28/20183/29/20183/29/2018APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in3/27/20183/28/20183/28/2018APART
DetailsTroy Cobbley
Piping as installed is ok and piping can be covered except around heads due to the plans indicating that all heads are fast responce. Only one of the new pendants is fast responce all others are standard responce. Heads need to match plans or modify plans to match install.

Phone #: ###-#### Inspection requested via web by Connie Danes