Permit Information
Permit NumberFIR18-00277
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION SE
Site Address 618 N ALLUMBAUGH ST
Project NameDarigold Office Remodel
Customer Number 
ePlanReviewYes
Description
[Darigold Remodel] - Quick Permit
Add, plug and relocate sprinklers to accommodate new wall and ceiling configuration.

[BLD17-01294]
Permit is to remodel an existing 2,155 sq. ft. office space to and 440 sq ft break area. This permit is approved contingent upon adhering to the approved plans on file. Work to include: demo existing nonbearing interior walls, relocating and installing new light fixtures, relocating mechanical grilles, new break room counter and sink, new interior non-bearing walls, new exterior windows and doors. Interior finishes must be in compliance with Ch. 8 of the 2012 IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JAR*
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/1/20186/4/20186/4/2018APASS
DetailsTroy Cobbley
Permit finaled

Brian Phone #: ###-####
INSP-Final Inspection5/17/20185/18/20185/18/2018AFAIL
DetailsTroy Cobbley
Project is not ready for a final yet. Need ceiling tile installed and the approved plans to verifiy where the quick responce heads are to b e placed. There is still an issue with mixing responces.


JCI rep is Fred Virgili Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in4/18/20184/18/20184/18/2018PPASS
DetailsTroy Cobbley
Tenting inspection passed. Piping can be covered.
INSP-Sprinkler Rough-in/Hydro4/11/20184/11/20184/11/2018PPART
DetailsTroy Cobbley
Overhead rough-in passed. I noted that the plans call for quick responce heads in the scope of work but not all heads are quick responce. I noted that a short corridor outside of the sprinkler scope of work appears to be in the building scope of work but has a standard responce head that is open to an area with quick responce heads. I noted a Storage room adjacent to the scope of work where the small room rule is being utilized which is not allowed. I noted another room in the building scope of work where two sidwall heads are located one above another and again are only standard responce. Piping is ok for cover since the above noted items can be verified at final. Tenting inspection is still needed.

Brian Phone #: ###-####