Permit Information
Permit NumberFIR18-00327
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 7500 W FAIRVIEW AVE
Project NameWestgate Shopping Center Shell
Customer Number 
ePlanReviewYes
Description
[Westgate Shopping Center Shell] - Quick Permit
Change antifreeze system to dry, add and relocate heads for demo'd walls and new demising wall. Riser modifications.

[BLD17-03244]
NO OCCUPANCY ALLOWED UNDER THIS PERMIT. TENANTS SHALL APPLY FOR CERTIFICATE OF OCCUPANCY PRIOR TO OCCUPYING THE SPACE. This building is fire sprinklered for area increase. Permit is to remodel an existing 68,500 sq. ft. building. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select bearing and nonbearing walls, removal of select door/door frames, removal of select overhang canopy, removal of select suspended acoustic ceiling, some site work, construction of select exterior CMU wall, select new exterior finish, construction of select interior non-bearing walls to create a riser room and a tenant demising wall, select new interior and exterior door/door frames, select new exterior storefront windows, select new suspended acoustic ceiling, electrical work, plumbing work, mechanical work and interior finishes in compliance with Ch. 8 of the 2012 IBC. Note: special inspection is required see attached #310 form. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/6/20189/7/20189/7/2018APASS
DetailsJim Page
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Final Inspection8/31/20189/4/20189/4/2018PCANC
DetailsTroy Cobbley
Not ready for final yet.

Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Final Inspection8/30/20189/4/20188/31/2018ACANC
DetailsTroy Cobbley
We would like to do it first thing in the morning if possible thanks. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in8/15/20188/15/20188/15/2018APASS
DetailsTroy Cobbley
Rough-in passed. Piping can be covered.

Should be done late morning. Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in6/25/20186/25/20186/25/2018PPASS
DetailsJim Page
New over-build on the southeast side of building has been filled with insulation, no fire sprinkler upright protection required in area filled with insualtion.

Please call Todd 30 minutes prior to arrival Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in/Hydro6/19/20186/20/20186/20/2018APASS
DetailsTroy Cobbley
24 hour air test on dry system passed

. Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in/Hydro6/18/20186/19/20186/19/2018APART
DetailsTroy Cobbley
24 hour air test dry system started at 8:00am with 43psi on the guage.
INSP-Sprinkler Rough-in/Hydro6/13/20186/14/20186/14/2018APASS
DetailsTroy Cobbley
Rough in for the dry system and hydro on dry system passed. Also the two new wet system branchlines passed.

Phone #: ###-#### Inspection requested via web by Sam Ball