Permit Number | FIR18-00328 |
Status | Finaled |
Name |
TREASURE VALLEY FIRE PROTECTION
|
Site Address |
1256 E EXCHANGE ST
|
Project Name | CHARLIES PRODUCE TI |
Customer Number | |
ePlanReview | Yes |
Description |
[Charlies Produce TI]
The fire sprinkler scope of work consists of installing new dry pendent sprinklers throughout the TI space per NFPA 13 for storage of class III commodities of up to 16'
Location on Plan - Bottom Left, Top Right
Commodity - Food
Classification - III
Storage Type (rack, solid pile, etc.) - Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - 8’
Height of Storage - 16’
Ceiling Height - 17’-10”
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - K=8.0
High Temperature Sprinklers Required - Yes
Applicable NFPA Section - F 16.2.1.3.2(c), Curve E, F 16.2.1.3.4.1
Hydraulic Design Criterion - .37/2000 - 65%, .24/2000
Hose Stream Requirements - 500
[BLD18-NA]
There does not seem to be an associated building permit at this time.
Alternative Materials and Methods:
• There are no AMM at this time.
|