INSP-Final Inspection | 10/3/2018 | 10/4/2018 | 10/4/2018 | A | PASS |
Troy Cobbley
|
|
|
Final fire alarm inspection complete.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 7/2/2018 | 7/3/2018 | 7/3/2018 | A | FAIL |
Jim Page
|
|
|
Tamper switches in vault are not hooked into the fire panel, wiring to vault is causing a ground fault.
Backflow valves are required to be electronically supervised.
Phone #: ###-#### Inspection requested via web by Nathan Price
|