Permit Information
Permit NumberFIR18-00419
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 8000 S FEDERAL WAY
Project NameMicron Building 17c Lobby
Customer Number 
ePlanReviewYes
Description
This is a design only project, the intent of this project is to show a relocated device and its new coverage. There does not appear to be an associated wuilding permit for this work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/31/20191/31/20191/31/2019PPASS
DetailsJim Page
Final fire alarm inspection for scope of work has been completed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection7/31/20188/1/20188/1/2018AFAIL
DetailsJim Page
Interniew rooms do not have any notifications installed, photo room needs notification installed, modifications have been made to the existing system (this permit as of this inspection is a design only pemit). Walls have been added in the restrooms blocking the current notification that is in place, modifications will be required.

As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price