Permit NumberFIR18-00501
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 355 W JULIA DAVIS DR
Project NameZoo Boise Bldg D7 E.O. Wilson
Customer Number 
ePlanReviewYes
Description
[Zoo Boise - D7 EO Wilson]
The fire sprinkler scope of work consists of a new wet system with 6” underground, 4 backflow preventer, riser, 2½” mains and 1½” lines. The building has various zoo exhibits. Most of the piping is steel and exposed. There is a small area of concealed CPVC.
• The underground piping is under permit FIR18-00477
[BLD17-03885]
Permit for the construction of a new 7,343 sq. ft. building with work to include a covered viewing area, two accessible restrooms and associated animal exhibits per the approved plans. This building is fully fire sprinklered.
Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.
• There are no AMM at this time which pertain to the fire sprinklers.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/13/20195/14/20195/14/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection complete.

George Jess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Supply line flush5/13/20195/14/20195/13/2019PCANC
DetailsJim Page
George Jess is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection5/10/20195/13/20195/13/2019PFAIL
DetailsJim Page
Provide dry sidewall under combustible over-hang above west exit. Replace upright fire sprinkler head that was painted in the south room behind habitat exhibit. Replace exposed CPVC to steel pipe. Change upright head in restroom to the required pendant head. Replace pendant head that is in FACP room with an upright head as discussed.

George Jess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection5/6/20195/7/20195/7/2019PFAIL
DetailsTroy Cobbley
No city approved plans or small documents on site. I noted that several branchline restraints are missing, chrome heads are missing in the Croc Display, FDC is not connected, FDC is too high, PIV is too high, need tags and signage, need sprinkler protection under the stairs as discussed, outside alarm bell is not at the FDC, PIV tamper is not working correctly. ......ect.

George Jess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro4/23/20194/24/20194/24/2019ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

George Jess is the contact, he wants this to be a 200 lbs hydro only inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro4/22/20194/23/20194/23/2019PCANC
DetailsJim Page
Cancelled per conversation with point of contact, will be rescheduled for a later date.

George Jess is the contact. He requests that this be a 200 lbs hydro only inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in3/27/20193/28/20193/28/2019APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler pipingt in otter and monkey exhibit complete, monkey and otter exhibit approved for cover.

George Jess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus