Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR18-00546
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 7672 W FAIRVIEW AVE
Project NameFLY HIGH TRAMPOLINE TI
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a trampoline park. There is a mezzanine below. This is a change of use. Therefore, current code applies.

[BLD17-03833]
This building is fully fire sprinklered to allow for area increase. Permit to remodel an existing 22,476 sq ft retail tenant space for a new fitness trampoline park. Work to include demo of interior non-structural partitions; new interior non-bearing walls; new elevated walkway platforms connecting trampoline areas; new mezzanine; new plumbing, electrical, and mechanical work; and new interior finishes in compliance with Ch. 8 of the 2012 IBC. Special inspections required per attached Form 310. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. **JAR**

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/201811/14/201811/15/2018PPASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Final Inspection11/14/201811/15/201811/15/2018APASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in/Hydro9/24/20189/25/20189/25/2018APASS
DetailsTroy Cobbley
Remaining piping rough-in for the northwest corner of the system where the ELO heads are located passed. Overhead hydro passed. I discussed the need for a forward flush test and permanant devices installed for this test.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in/Hydro8/23/20188/24/20188/24/2018PDONE
DetailsJim Page
Hydrostatic test for newly installed CPVC overhead fire sprinkler piping witnessed, no pressure loss observed at contractor provided gauge.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in/Hydro8/22/20188/23/20188/23/2018APART
DetailsJim Page
Rough to cover inspection for CPVC piping complete, CPVC piping approved for cover. Hydrostatic test to be completed at a later date.

Phone #: ###-#### Inspection requested via web by Connie Danes