Permit Information
Permit NumberFIR18-00548
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3022 S OWYHEE ST
Project NameOwyhee 24-Plex # 3022
Customer Number 
ePlanReviewYes
Description
[Owyhee 24-Plex #3022]
The fire sprinkler scope of work consists of three level 24-plex apartment building. The 4” underground supplies a 2” backflow preventer and header. The header is equipped with three 2” floor control valves. The floors have 2” mains and 1” branch lines of CPVC with residential sprinklers.

• The underground piping is under permit FIR18-00012.
[BLD17-02477]
Permit for a foundation only pending final review of the building plans the foundation has been approved in E-plan and is required to be on site for inspection. CDM

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/201811/14/201811/14/2018APASS
DetailsMike Jordan
above ground and underground Final Phone #: ###-#### Inspection requested via web by Stan Beus. final ok for remaining units. 107,108,207,208,307,308.
INSP-Final Inspection11/13/201811/14/201811/13/2018ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection11/2/201811/2/201811/2/2018PPART
DetailsTroy Cobbley
Sprinkler work passed for apartments 103, 104, 203, 204, 303, 304, 105, 106, 205, 206, 305, 306
INSP-Final Inspection10/19/201810/23/201810/24/2018APART
DetailsTroy Cobbley
The 12 apartments on the north end of the building are complete.

Colton Cox (###-####) or Jon Beazer ( ###-####) are the contacts for this final inspection. They are needing the inspection on 12 of the units or half of the project. We appreciate your help. Thank you.
Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro8/17/20188/20/20188/20/2018ADONE
DetailsJim Page
Hydrostatic test for level 1 witnessed, no pressure loss observed at riser provided gauge.

Overhead hydro Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro8/15/20188/16/20188/16/2018APART
DetailsTroy Cobbley
overhead hydro for the 2nd, 3rd and FDC passed. 1st floor failed due to leak.


Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in8/15/20188/16/20188/16/2018APASS
DetailsTroy Cobbley
Rough to cover for the piping in the soffits passed.

Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in7/23/20187/24/20187/24/2018APART
DetailsTroy Cobbley
First, second and third floor piping rough-in passed. Piping can be covered. Tenting for third floor piping passed. The only piping that can not be covered is the 2" risers at the third floor since they have not been "caped" as discussed to protect the piping from freezing.


OVerhead RTC Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in7/18/20187/19/20187/19/2018APART
DetailsTroy Cobbley
There were no plans for the first floor so the rough-in was not performed, second floor rough-in passed except for plans show a pendant in a bedroom entry that was not installed, third floor is missing a pendant head in a living room and some sort of "cap" is needed to retain heat in the shafts the 2" supply piping is installed in. In short the second floor sprinkler piping can be covered, the first and third can not be covered.


Robert Chambers is the contact for this rough to cover inspection. He will be at another job site so he will need advance notice when meeting time is. We are sorry for the inconvenience on the inspection scheduled the day before. We appreciate your help. Thank you Phone #: ###-#### Inspection requested via web by Stan Beus