Permit Information
Permit NumberFIR18-00590
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 13255 W MCMILLAN RD
Project NamePioneer Elementary Gym
Customer Number 
ePlanReviewYes
Description
[Pioneer Elementary Gym]
The fire sprinkler scope of work consists of adding in another riser to protect a gym, two classrooms, associate mechanical rooms and storage areas. The system is designed as a side feed.

[BLD18-00590]
Permit to construct a new 8,926 square foot addition with gymnasium, 2 classrooms and associated support areas including restrooms, office, storage, and mechanical rooms on the existing Pioneer Elementary School campus. Work also includes general site work. Special inspections required per attached Form 310. All work per the approved plans and notations. This building is fully fire sprinklered for area increase and is fully alarmed. **JAR**

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/26/201812/28/201812/28/2018APASS
DetailsTroy Cobbley
Permit finaled


Andrew Phone #: ###-####
INSP-Sprinkler Rough-in11/30/201811/30/201811/30/2018PPASS
DetailsTroy Cobbley
The remaining sprinkler piping is ok for cover

Contact Andrew Larson ###-#### 30 min prior to RTC Insp start...

Thought this was scheduled for AM but it didn''t save for some reason...

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in11/12/201811/13/201811/13/2018APASS
DetailsTroy Cobbley
See the city approved plans for rooms marked "ok" where sprinkler piping can be covered. I noted in a few rooms that the upright sprinkler protection is blocked by duct work and will need to meet the obstruction charts of NFPA 13
INSP-Sprinkler Rough-in10/31/201811/1/201811/1/2018APASS
DetailsTroy Cobbley
See the city approved plans for locations where piping above the hardlids is ok. I noted one earthquake brace needs to be re-positioned

Contact Andrew Larson - ###-#### 30 min prior to RTC Insp Start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in10/26/201810/29/201810/29/2018APASS
DetailsTroy Cobbley
The piping marked "ok" above the two restrooms and the common entry way for the restrooms is ok to cover.


Angie Phone #: ###-####