Permit Information
Permit NumberFIR18-00607
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 711 N CURTIS RD
Project NameST. ALS CENCOMPASS REHAB
Customer NumberUDG ONLY
ePlanReviewYes
Description
[Saint Aphonsus Rehabilitation Hospital - Cencompass- UDG Only] - Quick Permit
THIS IS AN UNDERGROUND ONLY AT THIS TIME. New 6"x75'± C-900 underground pipe , fitting and thrust blocks.

The fire sprinkler system is used for occupancy and building area increase. To construct a 49,821 square foot one story rehabilitation hospital with 40 sleeping units located near the Southwest corner of the intersection of Emerald Street and Curtis Road. Every sleeping unit including the associated toilet/shower room, except for the bariatric toilet/shower rooms, is required to comply as an “accessible unit” for the disabled. Work is to include reinforced concrete footings (continuous and spot), reinforced concrete monolithic stem walls and slabs on grade, protected exterior slab edge insulation, reinforced concrete piers, steel columns with steel base plates, steel braced frames, steel beams, open web steel bar joists, steel roof deck, steel roof top mechanical screen walls, membrane roof covering over rigid insulation, primary and secondary roof drains, steel stud exterior nonbearing walls, sandstone exterior veneer, EIFS, exterior metal panels, exterior windows, exterior doors, metal sun shade awnings, interior nonbearing walls, interior doors, interior windows, a 2-hr fire barrier wall to function as a horizontal exit, 1-hr smoke barrier walls to create smoke compartments, I-2 rated corridors, a Type I grease hood and duct system, a grease trap, millwork, and interior finishes. Activities that require Special Inspection include soils, concrete, masonry, steel (including welding and bolting), and anchors post-installed in hardened concrete. The concrete floor slab will be recessed at the walk-in cooler and freezer and at floor tile areas. In addition, a 7 foot tall masonry trash enclosure with plaster finish and tube steel gates, a 17 foot tall masonry emergency generator enclosure with plaster finish and steel louvers, a 17 foot tall masonry bulk oxygen enclosure with plaster finish and steel louvers, and a therapy garden with an elevated pavilion structure will be constructed. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/15/20195/16/20195/16/2019APASS
DetailsTroy Cobbley
permit finaled

Mike Phone #: ###-####
INSP-Supply line flush4/18/20194/19/20194/19/2019ADONE
DetailsJim Page
Underground main line flush complete.

THIS IS A 10:00 AM FLUSH WITH JIM PAGE AND STACIE FROM SUEZ WATER Phone #: ###-#### Inspection requested via web by Brad Bettencourt
INSP-Sprinkler Rough-in/Hydro1/15/20191/15/20191/15/2019PPASS
DetailsTroy Cobbley
Underground hydro test passed.
Phone #: ###-#### Inspection requested via web by Brad Bettencourt
INSP-Sprinkler Rough-in9/13/20189/13/20189/13/2018PPART
DetailsAdele J Schaffeld-Griffin
Inspection Comments from Forrest-Underground fire supply line from the point of connection at the municipal main to the IBR approved for bury. Refer to dated annotations on stamped plan set. Contractor to provide as-built plans as discussed to reflect the addition of two 45 degree ells. *Note- retainer glands installed in lieu of concrete thrust blocking. this is a underground cover inspection. troy nelson is or site contact Phone #: ###-#### >> Inspection requested via web by Brad Bettencourt