Permit NumberFIR18-00621
StatusFinaled
Name ALL VALLEY FIRE INSPECTIONS AND SER
Site Address 2141 W AIRPORT WAY
Project NameAirport Business Demo Agent Sy
Customer Number 
ePlanReviewYes
Description
1. MH Inergen Computer Room. To remove the Inergen tanks, manifold, pipes and blank off the manual pull/abort and horn strobe. The old Inergen release module will be left in the space and labeled for future use not in service. This action will effectively relegate the Ansul system into a pre-action only system for the pre-action system in the MH computer room. The old pre-action ceiling smoke detectors will be left operational.This system will still be monitored by the building fire alarm system.

2. Old Simplot FM-200 Computer Room. To remove the FM-200 system complete. Tank, manifold, pipes, control panel, smokes, pulls and horn strobes. This system was never monitored by the building fire alarm system. This space is protected by a wet sprinkler system. This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/16/20188/17/20188/17/2018PPASS
DetailsJim Page
Final inspection for demo work complete.