Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00623
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 3722 W ANDERSON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Cooking Hood Fire Extinguishing System: Hook up of a 9 gallon overlapping Ansul fire suppression system at Taft Elementary school.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/25/20192/26/20192/26/2019PPASS
DetailsJim Page
Final inspection for hood suppression system complete.

Richard Phone #: ###-####
INSP-Final Inspection2/22/20192/25/20192/25/2019ACANC
DetailsJim Page
Cnaclled per conversation with point of contact, inspection will be rescheduled for a later date.

Richard Phone #: ###-####
INSP-Final Inspection1/25/20191/28/20191/28/2019PCANC
DetailsTroy Cobbley
To be rescheduled per Richard Phone #: ###-####
INSP-Final Inspection1/11/20191/14/20191/14/2019AFAIL
DetailsJim Page
Hood suppression system did not report to the fire panel on system activation. Power to lights and outlets did not shunt when test link was cut.

Seth Phone #: ###-####
INSP-Final Inspection1/4/20191/11/20191/11/2019AFAIL
DetailsTroy Cobbley
Left message on voice mail. Went to job site and did not make contact. No inspection was performed.


Richard Phone #: ###-####