Permit Information
Permit NumberFIR18-00636
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2010 S HUDSON AVE
Project NameSkyline Apartments Bldg D
Customer Number 
ePlanReviewYes
Description
[Skyline Apartments Building D]
The fire sprinkler scope of work consists of installing a new fire sprinkler system into a new three level apartment building per NFPA 13R, 2016, and the City of Boise. The system has floor control valves, residential sprinklers and CPVC piping.

• The underground piping is under permit FIR18-00519.

[BLD17-04626]
The NFPA 13-R fire sprinkler system is used for occupancy and for story increase. To construct a 15,052 square foot three story VB Type of Construction apartment building (5,034 sq. ft. 1st story and 5,009 sq. ft. 2nd story and 5,009 sq. ft. 3rd story). Work is to include concrete footings, concrete foundations, concrete slabs on grade, wood stud bearing walls, wood stud shear walls, fiberglass shingles, fiber-cement board siding, manufactured stone veneer, 1-hr dwelling unit separations, 1-hour fire barriers for stair and breezeways, rated doors in breezeway, interior nonbearing walls, millwork, and finishes. Special Inspection is NOT required. The roof truss design is a deferred submittal item. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13-R as regulated by the Fire Department. Separate fire sprinkler permits shall be obtained prior to beginning any modification or installation work on such systems. **ajs**

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/31/20195/31/20195/31/2019PPASS
DetailsJim Page
Final underground supply inspection complete.
INSP-Final Inspection3/29/20194/1/20194/1/2019APEND
DetailsJim Page
Previousl;y noted items have been corrected, final fire sprinkler inspection complete.

Gerardo Arce is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection3/27/20193/28/20193/28/2019AFAIL
DetailsJim Page
Numerous overspaced issues throughout building next to kitchen, relocate hedas as discussed. Numerous heads to close to registers in restrooms, relocate head or provide intermediate temperature head in discussed locations. Provide heaqd box with required amount and style of heads.

Gerardo Arce is the contact. Thank you for the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in10/29/201810/29/201810/29/2018APASS
DetailsJim Page
All tenting in place at time of inspection, overehad fire sprinkler piping rough in complete, overhead fire sprinkler piping approved for cover.
INSP-Sprinkler Rough-in/Hydro10/26/201810/29/201810/29/2018ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping on levels 1, 2 and 3 witnessed, no pressure loss observed at riser provided gauges. Noted that glycerin anti-freeze was used to complete hydrostatic test.

Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in10/2/201810/3/201810/3/2018PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping on levels 1 and 2 complete, levels 1 and 2 approvbed for cover. Rough in inspection for level 3 complete, tenting still needs to be installed, level 3 not approved for cover.

Phone #: ###-#### Inspection requested via web by Stan Beus