Permit Information
Permit NumberFIR18-00654
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 1330 E EXCHANGE ST
Project NameDMS Fire main underground
Customer Number 
ePlanReviewYes
Description
(underground only) FDC will be placed on front of building, PIV will be remote see revised drawings, 6 inch Underground piping for future fire sprinkler system
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/12/20194/15/20194/15/2019PPASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Sprinkler Rough-in/Hydro4/12/20194/15/20194/15/2019APASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Supply line flush4/12/20194/15/20194/12/2019ACANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by Jessia Maxwell Inspection cancelled from web by: Jessia Maxwell
INSP-Sprinkler Rough-in/Hydro4/12/20194/12/20194/12/2019PPASS
DetailsTroy Cobbley
The underground hydro test was witnessed with no visible loss on the guage. Per conversation with the general contractor it appears that there will be adequate coverage for the underground supply piping when the asphalt has been installed. See previous entry for coverage concerns.
INSP-Supply line flush2/19/20192/20/20192/20/2019PDONE
DetailsJim Page
Undergournd main line flush complete.

Please call chris ford Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Sprinkler Rough-in/Hydro11/2/201811/5/201811/5/2018PPASS
DetailsTroy Cobbley
The remaining length of underground is ok for cover. Plans need to be resubmitted showing the new underground pipe routing. Also I spoke with the contractor about possible bury depth issues as previously noted.


Please call Clarncce Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Sprinkler Rough-in/Hydro10/31/201811/1/201811/1/2018PPART
DetailsJim Page
Partial rough to cover inspection for underground supply complete, area inspected today is the piping from the IBR and to the PIV and the section of piping to the west of the PIV to the change of direction. Area inspected approved for cover, remaining underground to be installed at a later date. A re-submittal will be required for the alterations made to the underground.

please call chris ford Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Sprinkler Rough-in10/4/201810/5/201810/5/2018APART
DetailsTroy Cobbley
Todays inspection was just for the 5' stub out which is passed. However exact dept of cover could not be verified. The top of the 6" pipe is located 4'-10" below the line where the blocks sit on the footing. There are two sewer/drain covers roughly 6' away from the pipe which have been place only 2'-10" above the pipe. If these covers are finish grade the the pipe is much too shallow and will need to be dug up and located at the correct depth. I spoke to the sprinkler designers who brought the plans and discussed my concerns and the implications if the pipe is too shallow. The 5' stub out is ok to cover but if too shallow will need to be corrected. No general contractor was on site to verify the actual final grade elevation.


For initial underground inspection Phone #: ###-#### Inspection requested via web by Jessia Maxwell