Permit Information
Permit NumberFIR18-00678
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 680 E BOISE AVE
Project NameD&B Supply Stockroom
Customer Number 
ePlanReviewYes
Description
[D&B Supply Stockroom]
The fire sprinkler scope of work consists of protecting a stock room with ESFR sprinklers. The system will be supplied by a new 750 Gpm @ 60 Psi fire pump. The system is designed as a small 6”x6”x3” grid.

Location on Plan - North
Commodity - Animal Food, Tools, Clothing, Machinery
Classification - Class I-IV
Storage Type (rack, solid pile, etc.) - Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - 6’-10’
Height of Storage - 18’
Ceiling Height - 23’-6”
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - ESFR
High Temperature Sprinklers Required - ESFR
Applicable NFPA Section - T 16.2.3.1
Hydraulic Design Criterion - K=25.2, 15#, 12 Sprinklers (4 on 3 lines)
Hose Stream Requirements - 250 Gpm


[BLD18-NA]
There does not seem to be an associated building permit at this time.

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/15/20198/20/20198/20/2019PPASS
DetailsJim Page
Final fire sprinkler inspection for scope of work complete.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Final Inspection8/9/20198/16/20198/15/2019ACANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
INSP-Final Inspection8/9/20198/12/20198/9/2019ACANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
INSP-Final Inspection3/22/20193/25/20193/25/2019ACANC
DetailsJim Page
Robert Phone #: ###-####
INSP-Sprinkler Rough-in3/20/20193/22/20193/22/2019PDONE
DetailsJim Page
Fire conference complete.

Phone #: ###-#### Inspection requested via web by Connie Danes