Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00680
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 4252 W ROSE HILL ST
Project NameOLIVE GROVE APARTMENTS
Customer Number 
ePlanReviewYes
Description
[Olive Grove Apartments II]
The fire sprinkler scope of work consists of two level 16-unit apartment building. The system has 2” underground piping, floor level control valves, a looped design, uses CPVC piping and residential sprinklers.

[BLD18-01080]
The NFPA 13R fire sprinkler system is used for occupancy. To construct a new 10,276 square foot apartment building (5,248 square feet 1st story and 5,028 square feet 2nd story) having a total of 16 dwelling units (8 units per story). All ground floor units are required to comply as Type B dwelling units with at least one ground floor unit also complying as a Type A dwelling unit. Work is to include concrete footings, concrete stem walls, concrete piers, concrete slab on grade with thickened sections at interior bearing walls, wood stud bearing walls, wood columns, wood stud shear walls with structural sheathing and hold downs, a 1-hr fire-resistance-rated 2nd story floor constructed of wood joists and wood sheathing, an egress balcony and stairways to serve the 2nd story, guards at the 2nd story, exterior doors and windows, cast stone exterior wall wainscot, exterior horizontal lap siding, exterior vertical board and batten siding, 1-hr fire-resistance-rated wood truss roof system with wood roof sheathing, attic draft stops, fiberglass shingles, interior nonbearing walls, 1-hr fire-resistance-rated dwelling unit separation walls, millwork, and finishes. Special Inspection is required for soils, steel connectors for wood, and for anchors post-installed in hardened concrete. The design for the roof trusses is a deferred submittal item. Existing Building C and the new building are considered to be one building. Both buildings are required to have an NFPA 13R fire sprinkler system, both buildings are required to be of Type V-A construction, and both buildings are required to have an R-2 type fire alarm system. The separation of existing Building C from the other existing buildings on site is required to comply with the 2015 IBC based on an imaginary property line drawn between them. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There is one AMM – Eliminates the need for extra floor level control valves.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/18/20196/18/20196/18/2019PPASS
DetailsTroy Cobbley
Permit finaled

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection6/12/20196/14/20196/14/2019AFAIL
DetailsTroy Cobbley
Provide the auto resetting tamper switches as discussed and the overhead and underground test papers.

please call James. Thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection6/10/20196/11/20196/11/2019PPART
DetailsJim Page
Partial final inspection for fire sprinklers complete, all escutcheons are placed with no gaps, permit addressing has been corrected. Could not complete inspection due to fire alarm contractor not requesting an inspection. Remaining items to inspect will be all fire alarm associated itmes with the fire sprinkler system. Per conversation with Ron Johnson, FDC bell will remain in current location.

Final inspection pending passing underground rough/hydro in AM. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro6/10/20196/11/20196/11/2019ADONE
DetailsJim Page
Undergorund hydrostatic test witnessed, no pressure loss observed. Underground repair approved for cover.

Underground rough/hydro after repair. Call James to coordinate Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Supply line flush6/10/20196/11/20196/11/2019ADONE
DetailsJim Page
Main supply flush completed on 10JUNE2019.

8am with Stacy at Suez. Call James if anything comes up Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Supply line flush6/10/20196/10/20196/10/2019PDONE
DetailsJim Page
Underground main line flush complete.
INSP-Supply line flush6/10/20196/10/20196/10/2019PFAIL
DetailsJim Page
Follow up coordination did not happen with SUEZ, no flush was performed, this request will need to be rescheduled and ccoordinated accordingly.

RE-flush at 2pm with Suez due to underground repair. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection5/31/20195/31/20195/31/2019PCANC
DetailsTroy Cobbley
Not ready for final. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Supply line flush5/31/20195/31/20195/31/2019PPASS
DetailsTroy Cobbley
I witnessed the underground supply line flush
INSP-Sprinkler Rough-in3/5/20193/6/20193/6/2019APASS
DetailsTroy Cobbley
Tenting has been repaired. Piping can be covered. Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in3/1/20193/4/20193/4/2019PFAIL
DetailsTroy Cobbley
Tenting failed again, not all piping has been covered. No piping to be covered until a tenting inspection has passed.

Call Anthony before you head out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in2/26/20192/27/20192/27/2019PFAIL
DetailsTroy Cobbley
Rough in passed with one exception on 2nd floor apt that Anthony will reseearch on possible obstruction. Tenting will need to be fixed in several areas lacking coverage. No piping to be covered,.

Call Anthony before heading out. Recheck based on Plan-Mod approval. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro2/19/20192/19/20192/19/2019PPASS
DetailsTroy Cobbley
Rough/hydro for the detached units passed. Piping can not be covered until a tenting inspection has been passed and plan mods are approved for the added pendant head in the second floor remote area. Call Anthony before heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro2/14/20192/15/20192/15/2019PPART
DetailsJim Page
Hydrostatic test for levels 1 and 2 overehad fire sprinkler piping witnessed, no pressure loss observed, no other inspections were perfromed.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro9/17/20189/17/20189/18/2018PPASS
DetailsTroy Cobbley
Underground rough/hydro. Call Anthony with a time, will be ready this morning Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello

_____________
Udg installation appeard to be adequate.
One hydro held fine, no loss.
The second hydro was low when I arrived. The contractor showed up and fixed a leak where the guage was connected. When I arrived the second time the UDG appeared to be holding pressure. I saw no visible leakeage.