Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00765
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 8485 S FEDERAL WAY
Project NameTEFFCO WAREHOUSE SHELL BUILDIN
Customer Number 
ePlanReviewYes
Description
[Federal Way Industrial Building]
The fire sprinkler scope of work consists of connection to the previously installed 8" dedicated underground fire service and install a new 1250 @130psi fire pump to supply the 3 new ESFR fire sprinkler systems, utilizing 6" and 4" mains with 2½” and 2" branch lines supplying 16.8k ESFR pendants to protect the 119,473 ft² core and shell building for rack or high pile storage up to 20 feet.

• This permit is for shell and core ONLY. There shall be NO occupancy under this permit.

Location on Plan - Warehouse
Commodity - Unknown (Core and Shell)
Classification - Group A Expanded
Storage Type (rack, solid pile, etc.) - Rack
Pallet Type (wood or plastic) - Wood
Aisle Width - 8’
Height of Storage - 20’
Ceiling Height - 40’
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - NO
Sprinkler Type - ESFR K=16.8
High Temperature Sprinklers Required - No
Applicable NFPA Section - T 17.2.3.1
Hydraulic Design Criterion - 52#, 3 rows of 4 sprinklers
Hose Stream Requirements - 250

[BLD18-00596]
This building is fire sprinklered in accordance with NFPA 13 with 60 ft yards for unlimited area. Permit for the construction of a new 117,432 sq. ft., 1-story concrete tilt-up shell building and associated site work. Scope of work includes: construction of slab on grade concrete foundation, concrete tilt up construction, construction of new steel bar-joist roof framing / steel pan deck, electrical, mechanical, plumbing. All work shall comply with the approved plans, DRH17-00143 and all applicable codes. Utilizes ANSI/ASHREA 90.1. Special Inspections Required, see form 310. A separate permit is required prior to occupying this structure and a separate racking permit is required if racks are installed over 8 feet in height. Separate permits will be required for the building fire protection systems, as regulated by the Fire Department. **JAR**

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/28/20191/30/20191/30/2019APASS
DetailsTroy Cobbley
Permit finaled

Contact is Tod Ketterling.
Thank you for all that you do! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in1/24/20191/25/20191/25/2019ADONE
DetailsJim Page
Fire pump commissioning complete.

Todd Ketterling is the contact for this inspection. He is needing a pump commissioning inspection. He is hoping for a call before hand to let him know what time appointment will be tomorrow so he can be ready. We thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro1/21/20191/22/20191/22/2019ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Todd Ketterling is the contact for this over head hydro. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in12/14/201812/17/201812/17/2018APASS
DetailsJim Page
Rough in inspection for overhead fire sprinkler associated with core and shell complete, any areas outside of corr and shell will require a cover inspection.

Todd Ketterling is the contact for this RTC inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus