INSP-Final Inspection | 1/14/2020 | 1/15/2020 | 1/15/2020 | P | PART |
Jim Page
|
|
|
No noted items for level 1 walkthrough.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
INSP-Final Inspection | 12/27/2019 | 12/30/2019 | 12/30/2019 | P | PART |
Jim Page
|
|
|
Walkthrough completed for remaining level 2 and basment level. Walkthrough not performed on level 1, base of A/V devices were masked for painting, could not see candella setting.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
INSP-Final Inspection | 12/12/2019 | 12/12/2019 | 12/12/2019 | P | PART |
Jim Page
|
|
|
Northside of level 2 walkthrough complete, approved plans are notated for areas of correction.
|
INSP-Final Inspection | 12/10/2019 | 12/12/2019 | 12/12/2019 | P | FAIL |
Jim Page
|
|
|
Level 3 floor plan does not match what was provided to the fire alarm designer, corrections need to be made for proper coverage..
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
INSP-Final Inspection | 12/4/2019 | 12/6/2019 | 12/6/2019 | A | PART |
Jim Page
|
|
|
Walk through complete for levels 4, 5 and 6, notated city approved plans with red ink for corrections.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
INSP-Final Inspection | 12/2/2019 | 12/3/2019 | 12/3/2019 | P | PART |
Jim Page
|
|
|
Walk through complete for levels 7 and 8, notated city approved plans with red ink for corrections.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
INSP-Final Inspection | 11/25/2019 | 11/27/2019 | 11/27/2019 | A | PART |
Jim Page
|
|
|
Walk through complete for penthouse and level 9, notated city approved plans with red ink for corrections, level 9 has a room that is a telephone room, not a telecom room, provide notification in telephone room. Conference room on level 9 is in a different location tahn the drawings, A/V device is overspaced due to wall location. Will verify correction on a future inspection.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|