Permit Information
Permit NumberFIR18-00883
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 3711 S COUNCIL SPRING RD
Project NameCouncil Springs
Customer NumberUDG ONLY
ePlanReviewYes
Description
[Council Springs Apartment - Udg Only] - Quick Permit
UG only - point of connection to be after Tee and Valve at property line. New 4"x66' ± C-900 Underground piping, fittings and thrust blocks. Other to install NRS Gate Valve in Roadbox. 13,071 Sq Ft 3 level Bldg.

[BLD18-01491]
Permit for the construction of a 3-story 11-unit wood framed apartment building with work to include general site work and construction of the new building per the approved plans. Carport to be constructed under separate permit, BLD18-03242. Special inspections required per attached Form 310. This building is fully fire sprinklered with an NFPA 13-R system as required for residential occupancy and story increase. **JAR**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/6/20199/6/20199/6/2019PPASS
DetailsJim Page
Final inspection for underground supply complete.

Contact Noemi Carrero ###-#### 30 min prior to UG Final Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in/Hydro4/25/20194/26/20194/26/2019ADONE
DetailsJim Page
Underground hydrostatic test witnessed, no pressure loss observed.

Contact Tyler Loomis ###-#### 30 min prior to Hydro insp start please.

Thx Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Supply line flush4/25/20194/25/20194/25/2019ADONE
DetailsJim Page
Underground main line flush complete.
INSP-Sprinkler Rough-in11/28/201811/28/201811/28/2018PPASS
DetailsJim Page
Rough to cover inspection for underground supply complete, approved for cover. noted that the underground supply was not routed the same as what the print showed due to valve location froim SUEZ, an as built will be required for submittal before final inspection to verify that the correct waterflow will work with the new pipe route, if figures do not work then corrections to the install will be required.

Contact Hunter Anderson ###-#### 30 min Prior to UG RTC insp start please, he would like to do this after 1 or 2 PM today if possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in11/27/201811/28/201811/27/2018ACANC
DetailsJim Page
Contact Hunter Anderson ###-#### 30 min Prior to RTC Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank