Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00903
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1180 S BROADWAY AVE
Project NameWENDY'S BROADWAY TI
Customer Number 
ePlanReviewYes
Description
[Wendy's Broadway TI] - Quick Permit
INSTALL 3 NEW HEADS OFF OF THE EXISTING 3" MAIN AND RELOCATE 1 PENDANT SPRINKLER IN THE SEATING AREA PER NFPA 13 2016 FOR LIGHT AND ORDINARY HAZARD. ALL EXISTING PIPING AND SPRINKLERS TO REMAIN IN PLACE.

There does not seem to be an associated building permit at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/8/20201/9/20201/9/2020APASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection is complete.

Adam Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Final Inspection11/19/201911/20/201911/20/2019PFAIL
DetailsJim Page
Flow switch did not report to fire panel during water flow.

Tom Small Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Final Inspection12/11/201812/12/201812/12/2018AFAIL
DetailsTroy Cobbley
Scope of work is complete but permit can not be finaled until the fire sprinkler system monitoring system has been installed and tested.

Adam Phone #: ###-####