INSP-Final Inspection | 6/17/2019 | 6/17/2019 | 6/17/2019 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 6/15/2019 | 6/17/2019 | 6/17/2019 | A | CANC |
Troy Cobbley
|
|
|
Contractor was not ready for inspection when I was. Contact Andrew Larson ###-#### 30 min prior to Fire Final Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 6/13/2019 | 6/14/2019 | 6/14/2019 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled when the fire alarm contractor is ready.
Contact Andrew Larson ###-#### 30 min prior to Fire Final Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 6/6/2019 | 6/7/2019 | 6/7/2019 | P | CANC |
Troy Cobbley
|
|
|
Still need the underground supply line hydro passed and the valve added on the discharge side of the pump. Need devices tested with the Fire Alarm Control Panel.
Contact Andrew Larson ###-#### 30 min prior to fire final insp start please.
Thank you Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 6/5/2019 | 6/6/2019 | 6/6/2019 | P | CANC |
Troy Cobbley
|
|
|
not ready for final
Contact Andrew Larson ###-#### 30 min prior to Fire Final Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 6/4/2019 | 6/5/2019 | 6/5/2019 | A | PART |
Troy Cobbley
|
|
|
Overhead hydro witnessed with no loss on the guage. The earthquake attachments have been addressed. I discussed with Andrew the requirements for NFPA 20, A.4.15.6, 4.12.1.3, ball drip in the test header line and piping the relief valve
Contact Andrew Larson ###-#### 30 Min prior to Hydro Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 6/3/2019 | 6/4/2019 | 6/4/2019 | A | NR |
Troy Cobbley
|
|
|
Not ready for hydro test due to modifications needed. I noted that the below mezzanine piping is not controled separately as per Boise Fire Prevention Code Chapter 12; 5-12-51 "Floor Control". Also it appears a control valve on the discharge side of the fire pump "note 22" has not been installed. I need to contact plan review on other items listed in NFPA 20 that may need to be addressed.
Apparently the fire pump certification was performed without a Boise City Representative present as required per NFPA 20 14.2.2. I requested to be present several times to the onsite sprinkler fitter and the general contractor.
Contact Andrew Larson ###-#### 30 Min Prior to RTC insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 5/28/2019 | 5/29/2019 | 5/29/2019 | A | FAIL |
Troy Cobbley
|
|
|
**Head spacing around 2 unit heaters needs adjusted. Heads need to be added under overhead doors that roll back(3). Fire pump not ready for start-up**MAS**
Contact Andrew Larson ###-#### Fire Pump Start-Up Insp, plan to a lot plenty of time for the inspection.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 5/28/2019 | 5/28/2019 | 5/28/2019 | P | CANC |
Troy Cobbley
|
|
|
Contact Andrew Larson ###-#### - Fire Pump Start-Up - please allow plenty of time for the Inspection. Andrew Larson has stated that Troy Cobbley has requested to be in attendance for this Inspection which is scheduled with Nickerson Pumps at 1 PM 5/28 Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in | 5/20/2019 | 5/21/2019 | 5/21/2019 | A | PART |
Troy Cobbley
|
|
|
Todays inspection was for the piping above the ceiling tile on the first floor. Piping can be covered except for where I need to verify the correct earth quake devices have been used.
Contact Andrew Larson ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 5/9/2019 | 5/9/2019 | 5/9/2019 | P | PART |
Troy Cobbley
|
|
|
The sprinkler piping above the hardlids on the first floor, Entry Lobby/Restrooms, is ok for cover. See the city approved plans for locations as marked "ok". We also spoke about obstructions to the ESFR heads and the solid shelf racking possibly being a problem. Contact Andrew Larson ###-#### 30 min prior to RTC Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 5/3/2019 | 5/6/2019 | 5/6/2019 | A | FAIL |
Troy Cobbley
|
|
|
Todays inspection was for the first floor hardlids. Piping can not be covered because the approved plans show 1 1/4" starters but 1" has been installed. Also no branchline restraints have been installed. There were no small documents or notes on site. I appears the trapeze bracing attachment rods are too small.
Contact Andrew Larson ###-#### 30 Min Prior to RTC Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|