Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00955
StatusFinaled
Name M2 AUTOMATION
Site Address 802 W BANNOCK ST
Project NameHistoric Hoff Building 8th Flr
Customer Number 
ePlanReviewYes
Description
8th Floor Remodel and Fire Alarm System Changes to Accommodate Remodel. This work is associated with building permit BLD18-04014.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/31/20192/1/20192/1/2019APASS
DetailsJim Page
Final fire alarm inspection for area of work complete.

Should be good to go. Neal ###-#### Phone #: ###-#### Inspection requested via web by Neal Timmerman
INSP-Final Inspection1/29/20191/30/20191/30/2019AFAIL
DetailsJim Page
Smoke detector in tenant space is to close to HVAC register, need to be 36 inches or more away to be code compliant. Room has been added, appears to be a small conference room per GC, need verification of room due to possible addition of speaker strobe to be code compliant.

Hi, we are ready for you. Give me a call to coordinate schedules. -Neal Timmerman ###-#### Phone #: ###-#### Inspection requested via web by Neal Timmerman