INSP-Final Inspection | 12/2/2019 | 12/3/2019 | 12/3/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Forward flush witnessed. Phone #: ###-####
|
INSP-Sprinkler Rough-in | 11/12/2019 | 11/13/2019 | 11/13/2019 | A | PASS |
Troy Cobbley
|
|
|
The area below the plattorm has been filled with insulation.
-Rick Phone #: ###-####
|
INSP-Conference | 11/5/2019 | 11/5/2019 | 11/5/2019 | P | DONE |
Troy Cobbley
|
|
|
The concealed space at the fire place can be enclosed. Per the building inspector the wood being used is fire treated.
on site conference for the fire place. rick fry is our contact person Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
INSP-Sprinkler Rough-in/Hydro | 10/25/2019 | 10/25/2019 | 10/25/2019 | A | DONE |
Jim Page
|
|
|
Hydrostatic test for wet systems complete, no pressure loss observed.
KERRY IS OUR FOREMAN. THIS IS A HYDRO AND COVER INSPECTION. Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
INSP-Sprinkler Rough-in | 10/25/2019 | 10/25/2019 | 10/25/2019 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for remaining overhead fire sprinkler piping above grid ceiling complete, approved for cover.
|
INSP-Conference | 10/15/2019 | 10/16/2019 | 10/16/2019 | A | DONE |
Troy Cobbley
|
|
|
Nacho, Rick and I discussed the fire place just inside the main entry. Per Nacho he will wrap the fire place with fire treated wood to be verified by myself and the building inspector. I also noted a raised platform has been built in the south east corner of the building that wil need to be addressed as far as a combustible concealed space. Rick Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 9/26/2019 | 9/27/2019 | 9/27/2019 | A | PASS |
Troy Cobbley
|
|
|
24 hour air test witnessed for the dry pipe system. // Ruddy Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 9/25/2019 | 9/26/2019 | 9/26/2019 | A | PART |
Troy Cobbley
|
|
|
200lb hydro test for the dry system witnessed with no pressure loss. The 24 hour air test started at 2:00pm with 44psi on the guage.
Rudy Phone #: ###-####
|
INSP-Sprinkler Rough-in | 9/17/2019 | 9/18/2019 | 9/18/2019 | A | PART |
Troy Cobbley
|
|
|
Piping in the building is ok for cover for the single head at the bottom of the stairs, second floor restroom and the Data room. I looked at the east side exterior canopy and the install looks good but the issue of galvanized piping came up and is currently being addressed with plan review. RUDY IS OUR FOREMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
INSP-Sprinkler Rough-in | 8/7/2019 | 8/8/2019 | 8/7/2019 | A | PASS |
Troy Cobbley
|
|
|
Rough-in passed on most of the remaining sprinkler piping. Just need another rough to cover for all piping above the lay-in tile, acouple of exterior canopies that are not built yet and some heads under the overhead doors. I noted a larger access door is needed for one of the inspector test/drum drip concealed in a walll. Door needs to be big enough for service. Rick Phone #: ###-####
|
INSP-Sprinkler Rough-in | 7/17/2019 | 7/18/2019 | 7/18/2019 | A | PART |
Jim Page
|
|
|
Rough in inspection for overehad fire sprinkler piping above hardlids complete, notated city approved drawings the 2 hardlids that are approved for cover. Non-combustible insulation needs to be installed between floor joist as noted on city approved drawings to cover OSB decking, insulation was not installed at time of inspection, these areas, as notated on city approved draiwngs, cannot be covered until insulation is installed and inspected for compliance.
inspection for cover at hard lids. Please call Rudy. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
INSP-Sprinkler Rough-in | 6/17/2019 | 6/18/2019 | 6/18/2019 | A | PASS |
Troy Cobbley
|
|
|
Todays inspection was for sprinkler system #2 in the "Show Room" area. Rough-in passed but plan mods will be needed to show all of the additional 90's in the branchlines and the ones in the mains. Pendants have not been installed. Mezzanine and Canopy piping has not been installed.
Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|