Permit Information
Permit NumberFIR18-00957
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 6772 W TARGEE ST
Project NameDENNIS DILLON RV
Customer Number 
ePlanReviewYes
Description
A COMPLETE SYSTEM INSTALLED IN NEW BUILDING FOR RV SALES AND REPAIR.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/2/201912/3/201912/3/2019APASS
DetailsTroy Cobbley
Permit finaled. Forward flush witnessed. Phone #: ###-####
INSP-Sprinkler Rough-in11/12/201911/13/201911/13/2019APASS
DetailsTroy Cobbley
The area below the plattorm has been filled with insulation.

-Rick Phone #: ###-####
INSP-Conference11/5/201911/5/201911/5/2019PDONE
DetailsTroy Cobbley
The concealed space at the fire place can be enclosed. Per the building inspector the wood being used is fire treated.


on site conference for the fire place. rick fry is our contact person Phone #: ###-#### Inspection requested via web by Brad Bettencourt
INSP-Sprinkler Rough-in/Hydro10/25/201910/25/201910/25/2019ADONE
DetailsJim Page
Hydrostatic test for wet systems complete, no pressure loss observed.

KERRY IS OUR FOREMAN. THIS IS A HYDRO AND COVER INSPECTION. Phone #: ###-#### Inspection requested via web by Brad Bettencourt
INSP-Sprinkler Rough-in10/25/201910/25/201910/25/2019PPASS
DetailsJim Page
Rough to cover inspection for remaining overhead fire sprinkler piping above grid ceiling complete, approved for cover.
INSP-Conference10/15/201910/16/201910/16/2019ADONE
DetailsTroy Cobbley
Nacho, Rick and I discussed the fire place just inside the main entry. Per Nacho he will wrap the fire place with fire treated wood to be verified by myself and the building inspector. I also noted a raised platform has been built in the south east corner of the building that wil need to be addressed as far as a combustible concealed space. Rick Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro9/26/20199/27/20199/27/2019APASS
DetailsTroy Cobbley
24 hour air test witnessed for the dry pipe system. // Ruddy Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro9/25/20199/26/20199/26/2019APART
DetailsTroy Cobbley
200lb hydro test for the dry system witnessed with no pressure loss. The 24 hour air test started at 2:00pm with 44psi on the guage.

Rudy Phone #: ###-####
INSP-Sprinkler Rough-in9/17/20199/18/20199/18/2019APART
DetailsTroy Cobbley
Piping in the building is ok for cover for the single head at the bottom of the stairs, second floor restroom and the Data room. I looked at the east side exterior canopy and the install looks good but the issue of galvanized piping came up and is currently being addressed with plan review. RUDY IS OUR FOREMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt
INSP-Sprinkler Rough-in8/7/20198/8/20198/7/2019APASS
DetailsTroy Cobbley
Rough-in passed on most of the remaining sprinkler piping. Just need another rough to cover for all piping above the lay-in tile, acouple of exterior canopies that are not built yet and some heads under the overhead doors. I noted a larger access door is needed for one of the inspector test/drum drip concealed in a walll. Door needs to be big enough for service.
Rick Phone #: ###-####
INSP-Sprinkler Rough-in7/17/20197/18/20197/18/2019APART
DetailsJim Page
Rough in inspection for overehad fire sprinkler piping above hardlids complete, notated city approved drawings the 2 hardlids that are approved for cover. Non-combustible insulation needs to be installed between floor joist as noted on city approved drawings to cover OSB decking, insulation was not installed at time of inspection, these areas, as notated on city approved draiwngs, cannot be covered until insulation is installed and inspected for compliance.

inspection for cover at hard lids. Please call Rudy. Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Sprinkler Rough-in6/17/20196/18/20196/18/2019APASS
DetailsTroy Cobbley
Todays inspection was for sprinkler system #2 in the "Show Room" area. Rough-in passed but plan mods will be needed to show all of the additional 90's in the branchlines and the ones in the mains. Pendants have not been installed. Mezzanine and Canopy piping has not been installed.

Phone #: ###-#### Inspection requested via web by Brad Bettencourt