Permit Information
Permit NumberFIR19-00006
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 1284 E BROADSTONE CT
Project NameKAHLE RESIDENCE
Customer Number 
ePlanReviewYes
Description
TFSS TO INSTALL A NEW NFPA 13D FIRE SPRINKLER SYSTEM IN THIS NEW SINGLE FAMILY DWELLING. Plan Mod 2/5/2019 Approved **MAS**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/11/20199/12/20199/12/2019APASS
DetailsJim Page
Previously noted items have been corrected, downstairs room labeled as pantry will stay as a pantry. Final fire sprinkler inspection is complete.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection9/5/20199/6/20199/6/2019ACANC
DetailsJim Page
Cancelled per conversation with point of contact, hole for sprinkler head relocate has not been patched, inspection request will be rescheduled for a later date.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection8/29/20198/30/20198/30/2019AFAIL
DetailsJim Page
Head in lower bedroom is 10ft 6 off of wall, needs to be 10 foot or less. Basement pantry is not a pantry, discussed room with Mark Stumbaugh, fire sprinkler plan reviewer and he agrees that room needs a sprinkler head. Irrigation needs to be active to test irrigation shutdown when flow switch activates, no flow test performed.



Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection7/29/20197/29/20197/29/2019PCANC
DetailsJim Page
Wrong permit was entered for inspection request, this inspection is cancelled, was not requested by this permit holder.

Matt Phone #: ###-####
INSP-Sprinkler Rough-in1/22/20191/22/20191/22/2019PPASS
DetailsJim Page
Tenting inspection complete, overehad fire sprinkler piping approved for cover.

Tenting inspection, please call Alicia before heading out to confirm it is ready. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in1/14/20191/14/20191/14/2019PPART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, areas requiring tenting not approved for cover until tenting install is inspected and approved.
INSP-Sprinkler Rough-in/Hydro1/11/20191/14/20191/14/2019PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed with antifreeze puped up to city pressure, no pressure loss observed.

Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello