Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00010
StatusFinaled
Name FIREXPERT
Site Address 204 N CAPITOL BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Cooking Hood Fire Extinguishing System: Swapping out old PCL 300 Tank, for new PCL 460 Tank.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/1/20192/5/20192/5/2019APASS
DetailsJim Page
Previously noted items have been corrected. Final hood supression system is complete.

3rd times the charm for the electrical trip test! Phone #: ###-#### Inspection requested via web by Don Kartchner
INSP-Final Inspection1/25/20191/29/20191/29/2019AFAIL
DetailsJim Page
Appliance under hood did not de-energize when hood system activated, per code all energy sources need to be isolated under the hood during system activation.

Coordinated with Jim Page, to do inspection at 8 am! Thanks!
-Zach w/ Firexpert. Phone #: ###-#### Inspection requested via web by Don Kartchner
INSP-Final Inspection1/24/20191/25/20191/25/2019ACANC
DetailsJim Page
Called point of contact but there was no answer, inspection request will need to be rescheduled, this request is cancelled.

Re-inspection of the electrical trip test. Phone #: ###-#### Inspection requested via web by Don Kartchner
INSP-Final Inspection1/21/20191/23/20191/23/2019AFAIL
DetailsJim Page
Power to little fryer on left did not isolate when suppression system was tripped, all energy needs to be isolated with hood activation. Hood has excessive build up of grease behind filoters, hood needs cleaned before next inspection.


I''m trying to do this final early in the morning, so they can still open up for regular business hours. Thank you! Phone #: ###-#### Inspection requested via web by Don Kartchner