Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00019
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 2400 S TRAPPER PL
Project NameHARRIS RANCH NORTH LOT 29
Customer Number 
ePlanReviewYes
Description
TFSS TO INSTALL A NEW NFPA 13D FIRE SPRINKLER SYSTEM IN THIS NEW SINGLE FAMILY DWELLING. Plan Mod Approved 2-5-2019 **MAS**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/26/20197/26/20197/26/2019PPASS
DetailsJim Page
Final fire sprinkler inspection complete.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection7/25/20197/25/20197/25/2019AFAIL
DetailsJim Page
Wiring for irrigation shutdown has not been installed correctly at sprinkler timer, due to this issue the final inspection for fire sprinklers will not be completed until landscape irrigation is complete and shutdown can be tested, flow switch was not tested.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in4/14/20194/15/20194/15/2019PPASS
DetailsJim Page
All tenting in place at time of inspection, overhead fire sprinkler piping approved for cover.

Remaining tenting, call James when heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in4/10/20194/11/20194/11/2019PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete. Partial tenting inspection complete, notated city approved drawings area above living room where tenting was not completed. Tenting in all other areas in place at time of inspection, all areas approved for cover except in living room area notated on city approved drawings that does not have tenting installed as of this note entry.

Tenting inspection, plans will be brought out in the morning, check with James on where they were tucked to keep out of the wind. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/11/20194/11/20194/11/2019ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

INSP-Sprinkler Rough-in/Hydro4/9/20194/10/20194/10/2019PFAIL
DetailsJim Page
Pressure at start of hydro was not the same PSI at end of hydro. On site plans do not have city approved stamp, no overhead inspection performed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello