INSP-Final Inspection | 4/19/2019 | 4/22/2019 | 4/22/2019 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
We are requesting that the inspection be at 1:00. Please call half hour prior to inspection to confirm Phone #: ###-#### Inspection requested via web by Heather Stier
|
INSP-Final Inspection | 4/19/2019 | 4/19/2019 | 4/19/2019 | P | CANC |
Jim Page
|
|
|
Please call a half hour before appointment to confirm. We would like our inspection done at 1:00pm Phone #: ###-#### >> Inspection requested via web by Heather Stier Inspection cancelled from web by: Heather Stier
|
INSP-Final Inspection | 4/16/2019 | 4/17/2019 | 4/17/2019 | A | FAIL |
Jim Page
|
|
|
Per alarm matrix on city approved drawings, paint booth is to be disabled during a general fire alarm, panit booth did not disable, panit prep room did. Provide knox box per note 12 of review comments. Fire sprinkler associated components have been tested and passed.
Confirm inspection 208.466.0613 Phone #: ###-#### Inspection requested via web by Cheyenne Zumstein
|