Permit Information
Permit NumberFIR19-00096
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 350 N 9TH ST
Project NameWater Bear T.I.
Customer Number 
ePlanReviewYes
Description
***QUICK PERMIT** INSPECTOR SEE NOTES ON PLAN**MAS** To add and relocate new sprinkller heads to new wall and ceiling locations.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/30/20195/1/20195/1/2019APASS
DetailsTroy Cobbley
Permit finaled

All finish pieces are on thank you Phone #: ###-#### Inspection requested via web by jeremiah robison
INSP-Final Inspection4/30/20194/30/20194/30/2019PFAIL
DetailsMark Scharfen
No escutcheons installed in kitchen or office. Jerimiah is going to install today.

If i am needed please give me a heads up. Thanks.
Jeremiah Robison Phone #: ###-#### Inspection requested via web by jeremiah robison
INSP-Sprinkler Rough-in4/4/20194/5/20194/5/2019APASS
DetailsJim Page
Rough to cover inspection for remaining area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by jeremiah robison
INSP-Sprinkler Rough-in2/27/20192/27/20192/27/2019PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, hardlids approved for cover.

Please give a heads up 30 min. if possible Phone #: ###-#### Inspection requested via web by jeremiah robison