Permit Information
Permit NumberFIR19-00159
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1445 W COMMERCE AVE
Project NameTBC Warehouse Upgrade
Customer Number 
ePlanReviewYes
Description
***INSPECTOR SEE NOTES ON PLANS**MAS** Install to new wet griided fire protection sytems in an existing warehouse, then demolish the two old pipe schedule fire protection systems. Racking Permit under BLD19-00343.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/17/20195/17/20195/17/2019PPASS
DetailsJim Page
Final fire sprinkler inspection complete.

Please call Troy with frame.

Thank you and have a great day. Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Final Inspection4/11/20194/12/20194/12/2019PFAIL
DetailsTroy Cobbley
Not ready for final due to delays caused by the door installer. I did perform a rough-in inspection for the south warehouse sprinkler system which passed.

Please cordinate final with Troy Nelson Phone #: ###-#### Inspection requested via web by Christophe Wilson
INSP-Sprinkler Rough-in/Hydro4/10/20194/11/20194/11/2019PCANC
DetailsJim Page
Cancelled per conversation with point of contact, overhead door not installed.

Please cordinate hydro with Troy Nelson Phone #: ###-#### Inspection requested via web by Christophe Wilson
INSP-Sprinkler Rough-in/Hydro3/29/20193/29/20193/29/2019PPASS
DetailsTroy Cobbley
The overhead hydro test for the south system passed.


Please Cordinate with Troy Nelson Phone #: ###-#### Inspection requested via web by Christophe Wilson
INSP-Sprinkler Rough-in3/26/20193/26/20193/26/2019PPART
DetailsJim Page
Rough in inspection for north warehouse system complete.

INSP-Sprinkler Rough-in/Hydro3/26/20193/26/20193/26/2019PPART
DetailsJim Page
Hydrostatic test for north warehouse system witnessed, no pressure loss observed.

This will be hydro and rough in for north warehouse system. Please call Troy Nelson with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham