INSP-Final Inspection | 7/8/2019 | 7/11/2019 | 7/11/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire alarm inspection complete.
Final with Eric from Crane Alarm ###-#### and Ken from Phoenix Fire. Requesting a Noon final inspection. Phone #: ###-#### Inspection requested via web by Fire Scheduler
|
INSP-Final Inspection | 7/1/2019 | 7/3/2019 | 7/3/2019 | P | FAIL |
Jim Page
|
|
|
Relocate horn/strobe in mens restroom on level 1 to correct coverage, relocate horn strobe in womans restroom basement level. Provide coverage at west en of basement level corridor. Lower horn strobe in southeast level 1 room. Provide monitoring for PIV. Provide coverage for room off of southeast basement classroom, area is marked storage, room is not a storage room. No device testing was done, need corrections made before sounding alarms.
Final inspection with Shilo Sprinklers ; Crane Alarm Please call Eric ###-#### with Crane Alarm to confirm actual time. Requesting for 11:00 am inspection. Phone #: ###-#### Inspection requested via web by Heather Stier
|
INSP-Final Inspection | 6/29/2019 | 7/2/2019 | 7/1/2019 | A | CANC |
Jim Page
|
|
|
I would like an 8:00am inspection to final the fire alarm system Phone #: ###-#### >> Inspection requested via web by Heather Stier Inspection cancelled from web by: Heather Stier
|