Permit Information
Permit NumberFIR19-00311
StatusFinaled
Name SONITROL PACIFIC
Site Address 5498 W ALBATROS LN
Project Name5498 Albatros
Customer Number 
ePlanReviewYes
Description
Provide fire sprinkler monitoring system to an existing fire sprinkler system that has 1 tamper switch and a pressure switch. This work is not associated with a building permit but is the result of an inspection to determine requirements for issuance of a Certificate of Occupancy under BLD17-02439.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/19/20196/20/20196/20/2019APASS
DetailsTroy Cobbley
Permit finaled

Please call 30min before to meet. Phone #: ###-#### Inspection requested via web by Kyle Burgess
INSP-Final Inspection5/17/20195/20/20195/20/2019PFAIL
DetailsTroy Cobbley
Provide correct tamper switch, provide the smoke detector with-in 5' of the panel on the wall as discussed, clear the trouble signal on the FACP as discussed, provide knox key box, provide testing of devices.

Please call 30min before so I can meet on-site Phone #: ###-#### Inspection requested via web by Kyle Burgess