INSP-Final Inspection | 7/23/2019 | 7/24/2019 | 7/24/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire alarm inspection complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 7/15/2019 | 7/16/2019 | 7/16/2019 | A | FAIL |
Jim Page
|
|
|
Correct smoke detector overspacing that is notated on the city approved drainwgs. Correct sync issue.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|