Permit NumberFIR19-00372
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 2717 S SIMSBURY LN
Project NameBENSCOTER RESIDENCE
Customer Number 
ePlanReviewYes
Description
NEW NFPA 13D FIRE SPRINKLER SYSTEM TO BE INSTALLED BY TFSS IN THIS NEW SINGLE FAMILY DWELLING.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/2/201910/2/201910/2/2019PPASS
DetailsTroy Cobbley
Permit finaled. Per contractor the irrigation system is separate and does not require the automatic shut off valve.

Please call James before heading out! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection9/30/201910/1/201910/1/2019PCANC
DetailsTroy Cobbley
Cancel per James. Bell is not working. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection9/9/20199/10/20199/10/2019PCANC
DetailsTroy Cobbley
Call James before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in7/1/20197/1/20197/1/2019APART
DetailsTroy Cobbley
Tenting passed. Piping can be covered. Still need as-builts.

Call James if there are any issues. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in6/27/20196/27/20196/27/2019AFAIL
DetailsJim Page
Sprinkler head in foyer is overspaced, head is more than 9 feet off of wall, spacing for this area is 16 X 16 so head needs to be a maximum of 8 feet off of wall. A wall has been added in the office, need to verify if the 20 X 20 spacing will work in this room with the new wall splitting the 2 heads shown on the city approved drawings. As-builts will be required for heads added for beam in entry hallway and changes to floor plan. No tenting installed at time of inspection.
INSP-Sprinkler Rough-in/Hydro6/27/20196/27/20196/27/2019PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed at 150PSI instead of the city static pressure, no pressure loss observed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello