INSP-Final Inspection | 12/4/2019 | 12/5/2019 | 12/5/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 | P | FAIL |
Jim Page
|
|
|
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.
FAs early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 | P | FAIL |
Troy Cobbley
|
|
|
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|