INSP-Final Inspection | 3/2/2020 | 3/3/2020 | 3/2/2020 | A | PASS |
Jim Page
|
|
|
Re-submitted plans reflect what is installed, final fire alarm inspection is complete.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 2/6/2020 | 2/7/2020 | 2/7/2020 | A | PART |
Jim Page
|
|
|
Final fire alarm inspection has been completed, candella needed to be adjusted in corner offices due to overspacing, as-builts will be submitted showing change. Permit can be signed off after as-builts are submitted, accepted and permit is back in issued status.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|