INSP-Final Inspection | 11/1/2019 | 11/1/2019 | 11/1/2019 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 10/28/2019 | 10/30/2019 | 10/30/2019 | A | FAIL |
Jim Page
|
|
|
Insulation above ceiling hanging down blocking upright head. 410 escutcheon missing in corridor leading to back door.
Call James before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 10/2/2019 | 10/2/2019 | 10/2/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items in area of work have been corrected, rough to cover inspection for overhead fire sprinkler piping is complete, approved for cover.
Please call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 9/27/2019 | 9/30/2019 | 9/30/2019 | A | CANC |
Jim Page
|
|
|
Point of contact cancelled inspection due to insulation not in place in areas where it was removed, insulation needs to be in place for sprinkler spacing.
Call James when heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 9/23/2019 | 9/25/2019 | 9/25/2019 | A | FAIL |
Jim Page
|
|
|
2 pendant heads are less than 4 inches from wall, a minimum of 4 inches is required per NFPA 13. All insulation needs to be in place and secured, insulation is blocking some of the upright heads.
Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|