Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR19-00838
StatusFinaled
Name STATE FIRE SALES & SERVICES
Site Address 999 W MAIN ST Unit: STE 1400
Project NameGalena Opportunity T.I.
Customer Number 
ePlanReviewYes
Description
**QUICK PERMIT** See note on plan** Installation of upright and concealed pendant sprinklers to cover new office area that is exposed to structure or beneath suspended ceiling.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/26/201912/27/201912/27/2019APASS
DetailsJim Page
Final fire sprinkler inspection for area of work complete.

Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
INSP-Sprinkler Rough-in12/19/201912/20/201912/20/2019PPASS
DetailsJim Page
Previously noted items have been corrected, rough in inspection is complete, hardlids approved for cover.

Contact: Steve Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
INSP-Sprinkler Rough-in12/10/201912/12/201912/12/2019AFAIL
DetailsJim Page
Walls do not go all the way to deck, sprinkler system needs to comply with 8.15.23 of the 2016 NFPA 13.

Contact: Steven Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore