Permit NumberFIR19-00846
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 7546 W STATE ST Unit: 120
Project NameClean Juice - TI
Customer Number 
ePlanReviewYes
Description
**QUICK PERMIT** Tenant Improvement to 1,453 Sq ft 1 level bldg Occupancy Class A 2, Const V B, Scope of work is to add or relocate heads to accommodate for new walls and ceilings.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/16/201912/17/201912/17/2019APASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.

Contact Hunter Anderson - ###-#### Final Insp - Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Final Inspection12/16/201912/23/201912/16/2019PCANC
DetailsJim Page
Contact Hunter Anderson ###-#### 30 min prior to Final Insp Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Final Inspection12/16/201912/17/201912/16/2019PCANC
DetailsJim Page
Contact Hunter Anderson ###-#### 30 min prior to Final Insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Final Inspection12/12/201912/13/201912/13/2019AFAIL
DetailsJim Page
2 pendant heads to close to registers, lees than 12 inches and 155 degree heads are placed. Head that was aded in juicer area is 3 5/8 inches off of wall, a minimum of 4 inches is required. Upright heads next to vetstibule entrance, northside are overspaced, upright heads are 10 on center, upright is 7 foot off of new wall and upright that was added is more than 5 foor off edge of new wall corner.

Contact Hunter Anderson ###-#### 30 min prior to Final Insp. start please, Hunter would like to sched. for early AM as possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in12/5/201912/6/201912/6/2019APASS
DetailsJim Page
Rough to cover inspection for area of work complete, 3 hangers to be relocated due to incorrect install, hangers are in prep/employee only area, north side above ceiling grid. Will verify hanger correction during next inspection request, cover is approved.

Contact Fred Silva ###-#### 30 min prior to RTC Insp. start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in11/25/201911/26/201911/26/2019APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping above serving line hardlid is complete, serving line hardlid approved for cover.

Contact Hunter Anderson 208###-#### 30 min prior to Hard Lid insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank