INSP-Final Inspection | 4/10/2020 | 4/10/2020 | 4/10/2020 | P | PASS |
Jim Page
|
|
|
Plans have been updated, head is shown in washer/dryer room on level 2. Final fire sprinkler inspection is complete.
Ready any time. As built approved with added head on second floor. Sheetrock patched and finished where extra head was added. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 3/24/2020 | 3/24/2020 | 3/24/2020 | P | PART |
Jim Page
|
|
|
Previously noted item has been corrected, final fire sprinkler inspection is complete, plans to be submitted to show addition of fire sprinkler head in washer/dryer closet on level 2. A follow up inspection request will need to be requested after plans reflect added head, once plans match install then permit can be finaled.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 3/23/2020 | 3/23/2020 | 3/23/2020 | A | FAIL |
Jim Page
|
|
|
Freeze protection/tenting no installed over new drop and piping to added head in washer/dryer closet, no cover until freeze protection is provided.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 3/18/2020 | 3/19/2020 | 3/19/2020 | A | FAIL |
Jim Page
|
|
|
Room labeled closet off of level 2 bonus room has washer and dryer hook-ups added, per 2016 NFPA13D section 8.3.8 requires sprinkler protection in areas containing washer/dryers, a cover inspection will be required for tenting verification.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 3/16/2020 | 3/16/2020 | 3/16/2020 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 12/26/2019 | 12/27/2019 | 12/27/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, rough to cover inspection for overhead fire sprinkler piping is complete, all tenting in place at time of inspection, cover is approved.
Overhead rough and tenting, call James before heading out - problem areas should be fixed by noon. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 12/23/2019 | 12/26/2019 | 12/26/2019 | A | CANC |
Jim Page
|
|
|
Per conversation with point of contact, insualtion is still not correct, inspection request cancelled before inspection was started, inspection will be rescheduled for a later date.
Overhead rough and tenting, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 12/23/2019 | 12/23/2019 | 12/23/2019 | P | FAIL |
Jim Page
|
|
|
Could not locate city approved drawings at time of inspection. Tenting needs corrected in numerous places before cover can be approved.
Ready any time, call James before heading out. Overhead rough and tenting inspection. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|